| Range of product | Modicon X80 | 
| Product or component type | Analog output module | 
| Electrical connection | 20 ways 1 connector | 
| Isolation between channels | Isolated | 
| Measurement error | <= 0.25 % of full scale 0...60 °C 0.1 % of full scale 25 °C  | 
| Temperature drift | 45 ppm/°C +/- 10 V 45 ppm/°C 0...20 mA 45 ppm/°C 4...20 mA  | 
| Common mode between channels | >= 80 dB | 
| Isolation voltage | 1400 V DC between channels and ground 1400 V DC between channels and bus 750 V DC between channels  | 
| Detection type | Open circuit 0...20 mA Open circuit 4...20 mA Short circuit +/- 10 V  | 
| Load impedance ohmic | >= 1000 Ohm +/- 10 V <= 500 Ohm 0...20 mA <= 500 Ohm 4...20 mA  | 
| Output level | High level | 
| Analogue output number | 4 | 
| Analogue output type | Current: 0...20 mA Current: 4...20 mA Voltage: +/- 10 V  | 
| Analogue output resolution | 15 bits + sign | 
| Supply | Internal power supply via rack | 
| Conversion time | <= 1 ms | 
| Maximum conversion value | 0...21 mA 0...20 mA 0...21 mA 4...20 mA +/- 10.5 V +/- 10 V  | 
| Fallback mode | Configurable Predefined  | 
| Protective treatment | TC | 
| Operating altitude | 0...2000 m 2000...5000 m with derating factor  | 
| Status LED | 1 LED (green)RUN: 1 LED per channel (green)channel diagnostic: 1 LED (red)ERR: 1 LED (red)I/O:  | 
| Net weight | 0.15 kg | 
| Power consumption in W | 3 W 24 V DC typical 3.2 W 24 V DC maximum 0.48 W 3.3 V DC typical 0.61 W 3.3 V DC maximum  | 
Analog 4 U/I Out Isolated